Overview
Models and specificationsTY-C-6W01B2Outline Dimensions (H × W × W)152 × 350 ×70 mmCommunication InterfaceTwo CAN interfaces, eight on-off active input interfaces, RS-485 interf...
Technical parameter table
Models and specifications | TY-C-6W01B2 | |||
Outline Dimensions (H × W × W) | 152 × 350 ×70 mm | |||
Communication Interface | Two CAN interfaces, eight on-off active input interfaces, RS-485 interface | |||
Networking Capability | Scalable to 20 circuits, 64 EPSs, and 3200 lamps | |||
Display Unit | 7" LCD display | |||
Installation method | Embedding (options include floor standing, piano-type, and wall-mounted) | |||
Loaded Communication Mode | CAN communication bus | |||
Power supply | 220 VAC 50 Hz (fire control power supply) | |||
Networking Distance | The bus is designed to transmit signal normally up to 1200 m, and optical fiber can be used when the communication distance is greater than 1200 m | |||
Runtime of standby power supply | ≥ 180 min | |||
Printer | Thermal printer | |||
Operating environment | Temperature: 0°C to 55°C, relative humidity: ≤ RH95% (without condensation) | |||
IP rating | IP30 |